Verwenden Sie den Reader unten, um das VänEE V160H75RS Klimaanlage Bedienungsanleitung zu lesen. Sie können die Anleitungen direkt auf der Seite durchblättern und die Funktionen unseres Readers nutzen, um alle wichtigen Informationen zur Installation, Bedienung und Wartung dieser VänEE Klimaanlage zu finden.

Bedienungsanleitung

Vollbild
Vollbild
Diese Anleitung teilen VänEE
War diese Anleitung hilfreich?

Fehlercodes

Nachfolgend finden Sie die Fehlercodes für den VänEE V160H75RS.

E01

E01 Supply damper range STEP 1: Unplug unit, inspect the damper system, remove any undesirable obstacle or dirt (fi lters and core may have to be removed to access the

E10

E10 Recirculation damper timeout damper system). Plug the unit. If STEP 1 did not fi x the problem, perform STEP 2: Open electrical

E11

E11 Recirculation damper compartment, check if connector J6 (blue) is well inserted, check for any

E02

E02 Supply damper timeout damper system). Plug unit.

E22

E22 Supply airfl ow STEP 1: Unplug the unit. Perform a visual inspection of the supply damper system. Clean fi lters, distribution registers and outside supply hood. Inspect

E23

E23 Supply motor (drive over current) STEP 1: Unplug/plug unit. If STEP 1 did not fi x the problem, perform STEP 2: Remove core and clear

E24

E24 Supply motor (drive over voltage) STEP 1: Unplug/plug unit. Under and over voltage may be detected with severe in-house power supply fl uctuation and stop the motor for protection.

E25

E25 Supply motor (drive under voltage) If STEP 1 did not fi x the problem, perform STEP 2: Replace the electronic assembly.

E26

E26 Supply motor (drive over temp) STEP 1: Validate if the air exchanger is exposed to ambient temperatures within the operating limits (see p. 4)

E27

E27 Supply motor (drive foc duration) the ventilation wheel from any dirt or obstacles. If STEP 2 did not fi x the problem, perform STEP 3: Disconnect J2 (white) and

E28

E28 Supply motor (drive speed feedback) connect a spare blower system. If it works, replace supply blower.

E29

E29 Supply motor (startup) assembly.

E03

E03 Supply damper If STEP 1 did not fi x the problem, perform STEP 2: Open electrical compartment, check if connector J5 (white) is well inserted, check for any

E32

E32 Exhaust airfl ow STEP 1: Unplug the unit. Perform a visual inspection of the exhaust damper system. Clean fi lters, distribution registers and outside exhaust hood. Make

E33

E33 Exhaust motor (drive over current) STEP 1: Unplug/plug unit. If STEP 1 did not fi x the problem, perform STEP 2: Remove core and clear the

E34

E34 Exhaust motor (drive over voltage) STEP 1: Unplug/plug unit. Under and over voltage may be detected with severe in-house power supply fl uctuation and stop the motor for protection.

E35

E35 Exhaust motor (drive under voltage) If STEP 1 did not fi x the problem, perform STEP 2: Replace the electronic assembly.

E36

E36 Exhaust motor (drive over temp) STEP 1: Validate if the air exchanger is exposed to ambiant temperatures within the operating limits (see p. 4)

E37

E37 Exhaust motor (drive foc duration) ventilation wheel from any dirt or obstacles.

E38

E38 Exhaust motor (drive speed connect a spare blower system. If it works, replace exhaust blower.

E39

E39 Exhaust motor (startup) assembly. E34 Exhaust motor (drive over voltage) STEP 1: Unplug/plug unit. Under and over voltage may be detected with

E40

E40 Outside air thermistor STEP 1: Check if thermistor is well connected in connector J7A. If STEP 1 did not fi x the problem, perform STEP 2: Disconnect connector J7A

E41

E41 Distribution air thermistor STEP 1: Check if thermistor is well connected in connector J7B. If STEP 1 did not fi x the problem, perform STEP 2: Disconnect connector J7B

E42

E42 PCBA thermistor fault STEP 1: Replace the electronic assembly. E43 PCBA temperature over limit STEP 1: Validate if the air exchanger is exposed to ambiant temperatures

E43

E43 PCBA temperature over limit STEP 1: Validate if the air exchanger is exposed to ambiant temperatures within the operating limits (see p. 4)

E05

E05 Exhaust damper range STEP 1: Unplug the unit, inspect the damper system, remove any undesirable obstacle or dirt (fi lters and core may have to be removed to access the

E50

E50 Wall control communication lost STEP 1: Unplug unit, inspect wires, plug unit. If STEP 1 did not fi x the problem, perform STEP 2: Remove wall control from

E51

E51 Wall control sensor STEP 1: Unplug unit, inspect wires, plug unit. If STEP 1 did not fi x the problem, perform STEP 2: Replace the wall control.

E06

E06 Exhaust damper timeout damper system). Plug the unit. If STEP 1 did not fi x the problem, perform STEP 2: Open electrical

E60

E60 Protection mode STEP 1: Perform general inspection of the unit (dampers, core, fi lters). 21

E07

E07 Exhaust damper compartment, check if connector J7 (red) is well inserted, check for any

E09

E09 Recirculation damper range STEP 1: Unplug the unit, inspect the damper system, remove any undesirable obstacle or dirt (fi lters and core may have to be removed to access the

Hilfe

Hast du Fragen zur Klimaanlage V160H75RS von VänEE? Stelle sie direkt unserem Experten! Du erhältst Informationen, praktische Tipps und maßgeschneiderte Lösungen in nur wenigen Sekunden.

Unten finden Sie Bedienungsanleitungen für Klimaanlage, die ähnlich wie V160H75RS sind. Versuchen Sie auch, alle VänEE Klimaanlage Bedienungsanleitungen anzusehen

Diskussion

Hinterlassen Sie einen Kommentar oder stellen Sie eine Frage

An der Diskussion teilnehmen

Stellen Sie eine Frage zum Handbuch oder fügen Sie eine hilfreiche Antwort für andere Nutzer hinzu.

Bitte geben Sie hier Ihre Nachricht ein
Bitte geben Sie Ihren Namen ein
Bitte geben Sie Ihre E-Mail-Adresse ein